I check the capacitor with a meter and it was good. The disconnected wasnt tripped outside. The compressor was still running so im still getting power outside. Contactor was passing proper voltage through it and also giving the 24 volts on the coil. Did notice when fan shuts off, the motor is really hot to the touch. I ohm out the motor and theres no open windings so it looked good. Had a amp meter and checked amp draw. The FLA for the motor is 1.3 when it shut off its 1.8. So thats probably why its hot,running too much amps through it. What would cause all this, someone please help!!