Question:

How can you tell if an appliance is energy efficient ?

by  |  earlier

0 LIKES UnLike

I was wondering how much electricity my electric kettle uses since it can boil water in 3 minutes and I thought that was quick. Is there a formula for calculating energy efficiency ?

 Tags:

   Report

2 ANSWERS


  1. If you can measure the energy out versus the energy in, an efficiency computation is trivial.  Electric kettles do not vary much in efficiency; none of them is very efficient since they all involve electric resistance heating, which is as inefficient as it is possible to get.  The total energy consumption of an electric kettle is small enough to not be very important, but if efficiency is your sine qua non, use a gas stove with a plain kettle to prepare your tea: it will save you a small amount of money.


  2. When referring to the efficiency of an appliance or energy system, we are actually talking about how much energy that system must use to perform a certain amount of work. The higher its energy consumption per unit of output, the less efficient the system is. For example, an air conditioner that requires 750 watts of electricity to provide 6,000 Btu of cooling will be less efficient than one that can provide the same amount of cooling for only 500 watts. The most common ratings applied to energy systems are EER and SEER for most central cooling systems; COP for some heat pumps and chillers; HSPF for heat pumps in their heating modes; and AFUE for gas furnaces and boilers.

    For more detailed explanations of the efficiency terms mentioned above, select any of the underlined topics below. If a topic is not underlined, it is not yet accessible. The CWLP website is undergoing continuous updating and expansion, so if the subject you are interested in is not yet available, please check back soon.

    EER

    SEER

    COP

    HSPF

    R-VALUE

    U-VALUE

    Top            Energy Services           Search This Site



    EER

    EER (energy efficiency ratio) is a measure of how efficiently a cooling system will operate when the outdoor temperature is at a specific level (usually 95° F). A higher EER means the system is more efficient. The term EER is most commonly used when referring to window and unitary air conditioners and heat pumps, as well as water-source and geothermal heat pumps. The formula for calculating EER is:

      Btu/hr of cooling at 95°  

    EER = ________________

      watts used at 95°  

    For instance, if you have a window air conditioner that draws 1500 watts of electricity to produce 12,000 Btu per hour of cooling when the outdoor temperature is 95°, it would have an EER of 8.0 (12,000 divided by 1500). A unit drawing 1200 watts to produce the same amount of cooling would have an EER of 10 and would be more energy efficient.

    Using this same example, you can see how efficiency can affect a system's operating economy. First, you'll need to determine the total amount of electricity — measured in kilowatt-hours — the unit will consume over a period of time. (A kilowatt-hour is defined as 1,000 watts used for one hour. This is the measure by which your monthly utility bills are calculated.) To do this, let's assume you operate your 8 EER window air conditioner — drawing 1500 watts at any given moment — for an average of 12 hours every day during the summer. At this rate, it will use 18,000 watt-hours, or 18 kilowatt-hours (kWh) each day, leading to a total consumption of 540 kWh over the course of a 30-day month. At a summer electric rate of 6.34¢ per kWh, it would cost you $34.24 to operate that window air conditioner each month. At the same time, a 1200-watt, 10 EER system, consuming 14.4 kilowatt-hours per day and 432 kWh per month, would cost you $27.39, a 20% savings over the less efficient model.



    Top            Energy Services           Search This Site

      

    SEER

    SEER (seasonal energy efficiency ratio) measures how efficiently a residential central cooling system (air conditioner or heat pump) will operate over an entire cooling season, as opposed to a single outdoor temperature. As with EER, a higher SEER reflects a more efficient cooling system. SEER is calculated based on the total amount of cooling (in Btu) the system will provide over the entire season divided by the total number of watt-hours it will consume:

      seasonal Btu of cooling

    SEER = ___________________

      seasonal watt-hours used

    By federal law, every central split cooling system manufactured or sold in the U.S. today must have a seasonal energy efficiency ratio of at least 10.0.



    Top            Energy Services           Search This Site



    COP

    COP (coefficient of performance) is the measurement of how efficiently a heating or cooling system (particularly a heat pump in its heating mode and a chiller for cooling) will operate at a single outdoor temperature condition. When applied to the heating modes of heat pumps, that temperature condition is usually 47°F. The higher the COP, the more efficient the system. COP can be calculated by two different methods. In the first, you divide the Btu of heat produced by the heat pump by the Btu equivalent of electricity that is required to produce that heat. This formula is stated:

      Btu of heat produced at 47°F

    COP = _________________________

      Btu worth of electricity used at 47°  

    For instance, let's assume a heat pump uses 4000 watts of electricity to produce 42,000 Btu per hour (Btu/hr) of heat when it is 47°F outside. To determine its COP, you would first convert the 4000 watts of electrical consumption into its Btu/hr equivalent by multiplying 4000 times 3.413 ( the number of Btu in one watt-hour of electricity). Then you would divide your answer — 13,648 Btu/hr — into the 42,000 Btu/hr heat output. This would show your heat pump to have a 47°F COP of 3.08. This means that, for every Btu of electricity the system uses, it will produce a little more than three Btu of heat when the outdoor temperature is 47°F.

    The second formula is most frequently used to determine chiller efficiency. Using this calculation method, you would divide 3.516 by the number of kilowatts (kW) per ton used by the system. This formula is stated:

      3.516

    COP = _____

      kW/ton

    For example, a chiller that consumes 0.8 kW per ton of capacity would have a COP of 4.4 (3.516 divided by 0.8). On the other hand, the COP of a new, more efficient chiller, using as little as 0.5 kW per ton, would be greater than 7 (3.516 divided by 0.5).



    Top            Energy Services           Search This Site



    HSPF

    HSPF (heating seasonal performance factor) is the measurement of how efficiently all residential and some commercial heat pumps will operate in their heating mode over an entire normal heating season. The higher the HSPF, the more efficient the system. HSPF is determined by dividing the total number of Btu of heat produced over the heating season by the total number of watt-hours of electricity that is required to produce that heat. The formula is written:

      Btu of heat produced over the heating season

    HSPF = __________________________________

      watt-hours of electricity used over the heating season

    Most heat pumps installed in Springfield today have HSPFs in the 7.0 to 8.0 range, meaning they operate with seasonal efficiencies of anywhere from 205% to 234%. (To convert the HSPF number into a percentage, you just divide the HSPF by 3.414, the number of Btu in one watt-hour of electricity.) That means that, for every Btu-worth of energy they use over the entire heating season, these systems will put out anywhere from 2.05 to 2.34 Btu of heat. Compare this to electric furnaces, which have nominal efficiencies of 100% (for each Btu worth of electricity, they put out one Btu of heat), or new gas furnaces, which have efficiency ratings of about 80% to 97% (for each Btu worth of gas, they put out 0.8 to 0.97 Btu of heat).

    NOTE:When comparing energy systems that use different primary fuel sources with different costs per Btu, it is important that you understand that higher operating efficiency is not necessarily equivalent to better operating economy. Although an electric heat pump might work with greater efficiency than a gas furnace, it won't necessarily be more economical to run due to the pricing difference between the two fuel sources.



    AFUE

    AFUE (annual fuel utilization efficiency) is the measurement of how efficiently a gas furnace or boiler will operate over an entire heating season. The AFUE is expressed as a percentage of the amount of energy consumed by the system that is actually converted to useful heat. For instance, a 90% AFUE means that for every Btu worth of gas used over the heating season, the system will provide 0.9 Btu of heat. The higher the AFUE, the more efficient the system.

    When comparing efficiencies of various gas furnaces, it is important to consider the AFUE, not the steady state efficiency. Steady state refers to the efficiency of the unit when the system is running continuously, without cycling on and off. Since cycling is natural for the system over the course of the heating season, steady state doesn't give a true measurement of the system's seasonal efficiency. For instance, gas furnaces with pilot lights have steady-state efficiencies of 78% to 80%, but seasonal efficiencies B AFUEs B closer to 65%.

    Virtually all gas forced-air furnaces installed in this area from the 1950s through the early 1980s had AFUEs of around 65%. Today, federal law requires most gas furnaces manufactured and sold in the U.S. to have minimum AFUEs of 78%. (Mobile home furnaces and units with capacities under 45,000 Btu are permitted somewhat lower AFUEs.) Gas furnaces and boilers now on the market have AFUEs as high as 97%.



    Top            Energy Services           Search This Site



    R-Value

    R-value is the measurement of how effectively a material resists the transfer of heat via conduction. The higher the R-value, the less heat transfer can take place.

    Some materials are more resistant to heat transfer than others, giving them higher R-values. One of the best ways to enhance the product's R-value is to increase the amount of gas (including air) inside or immediately surrounding it. For instance, the glass of a single-pane window has virtually no R-value, but the thin film of air that normally exists on either side of the glass gives the window an R-value of about 0.83. Adding a second pane of glass and sealing the space between the panes will increase the thickness of one of the insulating gas layers, thereby more than doubling the window's R-value.

    Another example of how the presence of dead-air spaces affect a product's R-value can be seen with wood. Hard woods, like oak, typically have an insulating value of R-1 per inch of thickness. However, softer woods, such as pine, might have R-values twice as high due to their greater number of air-filled pores.

    Products developed especially for the purpose of impeding unwanted heat transfer are called insulation. Insulation can be made of a variety of materials, including old newspapers and wood fibers, glass fibers, and synthetic foams. It can also come in a variety of configurations, including soft blankets, rigid boards, or fluffy granular loose-fill, but what they all have in common, is their abundance of air-filled pores or pockets.

    The actual R-value of insulation products can vary greatly, depending on their composition and form. The least resistant and least common are perlite and vermiculite loose-fills, at R-2.2 to R-2.7 per inch of thickness; the most resistant are polyisocyanurate rigid boards, at R-7 per inch of thickness. Fiberglass blankets and cellulose loose-fills, two of the most common residential insulations have R-values of 3.1 to 3.7 per inch.

    The CWLP Home Efficiency Handbook contains more information about R-value as it applies to insulation products.



    Top            Energy Services           Search This Site



    U-Value

    U-value is the measurement of how much heat can be conducted through a building component (such as a wall or window). As such, it is the opposite of R-value, which measures the ability of material to resist heat conduction. The higher the U-value, the more heat the material(s) will allow to be transferred through it. The lower a material's U-value, the higher its R-value will be. U-values are always expressed in decimals (e.g., U-0.166).

    To determine the R-value of a product for which the U-value is given, you first convert the U-value to its equivalent fraction and then invert it. For instance, the equivalent fraction of U-0.166 would be 166/1000 or 1/6. This inverts to 6/1 or 6, giving you an R-value of 6.

    For most consumers, U-value is likely to be of concern only when shopping for new windows, where efficiency is frequently stated in terms of U-value rather than R-value

Question Stats

Latest activity: earlier.
This question has 2 answers.

BECOME A GUIDE

Share your knowledge and help people by answering questions.