Question:

How do I get a 240V stinger leg down to 120V?

by  |  earlier

0 LIKES UnLike

This is and old system out dated electrical system. Well this is a 120/208v panel and the panel is pretty full. I have three spaces left, a-phase 120v, b-phase 120v, c-phase 240v. how do get the C-phase to 120V. for my swamp cooler?

 Tags:

   Report

4 ANSWERS


  1. You would need a transformer to do that. Another solution is to add a small sub panel so you have more breaker space. The panel you have is a high leg 120 configuration that was quite common 60 years ago. Call a qualified professional electrician to add a small sub panel and to tap 2 of the 120 legs and the neutral. Do not try to use the high leg.


  2. If you're talking about 'center tapped delta' you can't

    use that C phase for 120V.

    If you've got a three phase panel, and are seeing 240V. Phase to Phase,

    and 120V.  A-N, and B-N, that's what you've got.

    If you're out of circuits, an electrician can give you a sub panel to

    supply a few more. - Tell him what you've got.

    Cheaper than a transformer.

    Messing with this system is not a DIY project unless you know what you're doing.

    It's not in most textbooks.

  3. The best possibility is to evaluate the load on existing circuits and free up an additional 120 space, , as the only way to step down from the 208 is via transformer which in this instance is not a cost effective approach. Your swamp cooler quite possibly could be dual voltage and be rewired to run 208 as well. I bet you have a circuit that is very lightly loaded that could share an existing breaker location.

  4. If you are in the US the only ABC phases are for 3 phase which is commercial. Since you have a- phase spare why not use it??

Question Stats

Latest activity: earlier.
This question has 4 answers.

BECOME A GUIDE