0 LIKES LikeUnLike
I am working on a Brush Induction generator in West Africa. The polarisation index test is just below 2. I’m injecting 5,000 VDC using a Fluke 150B. The generator typically produces 22MW at base load. Its rainy season here (aprox. 28 deg C) and the alternator has been stood a couple of months within an enclosure for a few months without heaters. I am now able to run the heaters for approximately 12 hrs per day but that is all. I have the possibility of using a large welding machine on site. The results have not really improved during the last week, do I need to be more patient or try something else. Before this unit was moved the PI value was 3.5.
Tags:
Report (0) (0) | earlier
Latest activity: earlier. This question has 2 answers.