Question:

How to calculate theoritical size of electric heater (KW) for air heating?

by  |  earlier

0 LIKES UnLike

I want to calculate the size of electrical heater for 1000 cubic meter air flow from 30 C to 120 C temperature. Can anyone tell me the formula for it... I hv surf all websites and all search engines but didn't find this details.

 Tags:

   Report

2 ANSWERS


  1. specific heat capacity of dry air is 1.006 kJ/kgC

    Density of air at 30C is 1.165 kg/m³

    1000m³ x 1.165 kg/m³ = 1165kg, weight of the air

    energy to heat the air in Joules:

    E = 1.006 kJ/kgC x 1165kg x 90C = 105,480 J <---- error, see below

    Now you need the flow rate, which you omitted.

    if the air flow changes the air every minute, a fast flow, then the

    power (energy per second) is

    P = 105,480 J / 60 sec = 1758 J/s = 1758 watts

    which is the size of the heater.

    edit, correct arithmetic mistake. missed the kJ in energy equation.

    Corrected versions:

    energy to heat the air in Joules:

    E = 1.006 kJ/kgC x 1165kg x 90C = 105,480 kJ

    Now you need the flow rate, which you omitted.

    if the air flow changes the air every minute, a fast flow, then the

    power (energy per second) is

    P = 105,480 kJ / 60 sec = 1758 kJ/s = 1758 kW

    which is the size of the heater.


  2. I can tell you what it is in imperial units, you would have to convert it from Celsius to Fahrenheit and from cubic meter/minute (you do not have a time rate on your air flow, which it must have or it is a volume) to cubic feet/minute, and then convert your answer from Btuh to KW.

    The formula is Q = Btuh/(1.08*(t2-T1))

    Q = air flow in Cubic Feet per Minute

    Btuh = heating capacity

    t2 = 120C converted to F

    t1 = 30C converted to F

    rearrange and get CFM*1.08*(t2-t1) = heating capacity required in Btuh, then convert it to KW.

Question Stats

Latest activity: earlier.
This question has 2 answers.

BECOME A GUIDE

Share your knowledge and help people by answering questions.