Question:

I HAVE 10 INDUCED MOTOR I WANT BUY ATRANFORMER FOR SUPPLY WHO CALCULATE IMPEDANCE VOLTAGE DROP and rated po

by  |  earlier

0 LIKES UnLike

AND WHO CALCULATE RATED POWER OF TRANSFORMER

RATED POWER OF INDUCED MOTOR=1O KW

DISTANCE TRANSFORMER OF EACH MOTOR =100M

 Tags:

   Report

2 ANSWERS


  1. This is even less clear than your last question.

    And all caps make it difficult to read.

    Get someone to translate it to english for you.

    AND provide the needed information.


  2. I am writing this just to give some idea because nothing is known.Voltage range,what kind of cable,what is the cross section of the cable?10 motors,10kW each ( as much as I understand) and the distance for each motor to transformer is 100 mt.

    If the voltage range is 380Volts and three phase feeding.According to our regulations voltage drop is allowed up to %3.According to power you must use 4x6 mm2 cable.Than  voltage drop %will be 0,0206 ( than you will have 7,83 Volt voltage drop. 380- 7,83= 372,16 volt at the motors)