Question:

Seimens 611U Problems?

by  |  earlier

0 LIKES UnLike

Dear Sir

I am an Automation Engineer. I work for AVAND GRP Pipe Co. at Ahwaz -Iran. We have some problems with one of the GRP Pipe Machine that use SIEMENS SIMODRIVE 611 U .Drive Specifications that used explain below

When we have no load on gearbox side then motor can speed up to maximum speed.

But After coupling normal load gearbox motor start with normal ,speed can be increased only up to about 700 rmp (%30 of maximum speed) beacuase I/R module go to fault(DC-LINK Over Voltage Fault) and at same tme drive module stay at RUN mode. If you increase load more, then in lower speed I/R module go to fault (DC-LINK over Voltage)

I/R In feed Module 6SN1145-1BA02-0CA1

Motor 1FT6105-8AC71-1AB1

Power Module 6SN1123-1AA00-0DA1

Control Module 6SN1118-0NH00-0AA0

Line Filter For I/R Module 1P6SL3000-0BE23-6AA0

I think coupling of motor with gear box is weak & not so good .

.I will be very happy if you can help us to solved

Best Regards

Hossein Bijeh

E-mail:hosseinCijeh@gmail.com

 Tags:

   Report

2 ANSWERS


  1. Thre can be two possible problems

    1) Either you have not entered the ratings of your motor correctly in the drive settings.

    2) there is a percentage slip compensation setting - it might  not be properly set

    If you are beneffited Please let me know by rating my answer.


  2. Good letter. Hope you sent this to the company. With a letter like this you are sure to get a positive response.