Question:

What is the correct size Circuit breaker for the input of a 12KVA 208 V UPS?

by Guest33571  |  earlier

0 LIKES UnLike

What is the correct size Circuit breaker for the input of a 12KVA 208 V UPS?

 Tags:

   Report

3 ANSWERS


  1. If Yayha doesn't know, he should just say so.

    60 amps should do.


  2. well lets c

    in sizing a CB for UPS, certain measures should be taken during calculations, according to the standard u are following

    but anyway generally u have:

    design current= S/(1.732xVxcosPHI)

    where V is the line to line voltage, and cosPHI is the power factor

    now to get the CB rating:

    u multiply the design current by 1.1 or 1.25 according to the standards u r following

    but, its all a matter of sense and practice

  3. Current for a 12000va ups is 57.69 at 208 volts. SO the appropriate circuit breaker is 60 amperes, 2 poles.